To Make Enquiries
Via Email: Please click on this link → HERE
Via WhatsApp: Please click on this link → HERE
Descriptions
Modern, cost-effective DC drive with excellent system intergration flexibility
- 25 A – 7,400 A (5hp – 6,500 hp)
- 24 V – 480 V | 575 V | 690 V
- Control Technique’s Mentor MP brings DC drive technology up to date, enabling existing and new DC motors to provide economic and productive service.
- DC drive technology remains cost-effective, efficient and is relatively simple to implement.
Related Documents
Mentor II User Guide
Control Techniques - Mentor MP DC Drive - Advanced User's Guide
Mentor MP brochure
Features
Flexible system integration
Mentor MP is a modern DC drive based on Control Technique’s current AC drive technology. This means that Mentor MP inherits the system integration flexibility such as:
- Three option module slots for automation control, I/O, feedback devices and communications
- SmartCard for PLC program and parameter storage
- Software tools for easy configuration and monitoring
Technology for reliability and performance
Mentor MP takes a step foward in performance, robustness and reliability.
High performance motor control:
- Galvanic isolation(patent pending) between power and control protects the control circuits and other equipment connected to the drive from the high voltages on the power circuit. This feature is unique on DC drives
- Protection system against poor quality industrial power supplies and lightning strikes
- Integrated drive and motor protection
Flexible field control
Internal field controller with intelligent field weakening means that 90% of applications require no additional external controller:
- Integrated field control on frame size 1 to 8 A
- Integrated field control on frame size 2 to 20 A
- Flux control for enhanced open-loop performance
- External FXMP25 field control to 25 A
Easy upgrade
Mentor MP has been designed as an easy upgrade for Mentor II. It has the same physical dimensions and power connection layout. Software tools have been developed to easily migrate to the new platform.
Specifications
- Models available for two or four quadrant (regenerative) operation
- 25 A to 7400 A, 24 V – 480 V | 500 V – 575 V | 500 V – 690 V
- Optional high-brightness LED or multi-language LCD keypad, simple configuration using plain text
- 12/24 pulse operation to minimize harmonics
- IP20 (NEMA 1) protection for size 1, IP10 (open chassis) for size 2A and 2B, and IP00 (open chassis) for size 2C and 2D for easy, low cost installation
- Integrated drive and motor protection for:
- Over current
- Over temperature
- Phase loss
- SCR / Thyristor junction temperature
- Feedback loss
- Field loss
- Armature open circuit
- Internal field controller with intelligent field weakening means that for 90% of applications no additional external controller is required
- Frame size 1 to 8 A
- Frame size 2 to 20 A
- Flux control for enhanced open loop performance
- Optional FXMP25 external field controller for current fields up to 25 A
- Digital link for field control from Mentor MP or Mentor II
- Standalone digital control mode for simple application
- Flux control for enhanced open loop performance
- Intelligent field weakening
- Field forcing – for high dynamic machine reversal
- Field reversal – low dynamic machine reversing using two quadrant main stack
- Mentor MP size 1 can be used for field greater than 25 A
- Serial port for Modbus RTU and PC communications.
- 3 Universal option module slots, allowing Mentor MP to benefit from the solutions developed for Control Technique’s market leading AC drive technology.
Each option slot allows:
- High performance PLC and motion control
- Ethernet and Fieldbus communications
- Connectivity to additional feedback devices
- Additional I/O
- Galvanically isolated control
- Smartcard for drive parameter back-up and copying, allowing rapid installation and maintenance
- Integrated PLC as standard
- Standard software features for easy integration
- PID controller
- Motorized potentiometer
- Digital lock (Slave operation from master encoder)
- Open loop control using estimated speed advanced processing based on armature voltage and field flux feedback
- Closed loop control using
- Tacho-generator feedback for connection to traditional DC motor
- Incremental encoder feedback for higher accuracy and position control
- Optional SinCos, SSI, Hiperface and EnDAT connectivity for high performance applications
- High performance control strategy
- 32 bit microprocessor
- 35 μs current sampling time
- Speed controller and ramps update 250 μs
- Autotune features for armature, field current loops and speed
Ratings
Current ratings
The power ratings for the 230 V, 480 V, 575 V and 690 V configurations are shown below.
The continuous current ratings given are for a maximum ambient temperature of 40 °C (104 °F) and an altitude of 1000 m (3,300 ft). For operation at higher temperatures and altitudes de-rating is required. Overload of 150 % for 30 s is available with ambient temperature of 40 °C (104 °F) up to a maximum of 10 repetitions per hour.
480 V ratings
Model |
AC INPUT CURRENT |
DC OUTPUT CURRENT |
TYPICAL MOTOR POWER |
CONTINUOUS |
CONTINUOUS |
150% OVERLOAD |
@ 400 Vdc |
@ 500 Vdc |
MP25A4(R) |
22 A |
25 A |
37.5 A |
9 kW |
10 hp |
MP45A4(R) |
40 A |
45 A |
67.5 A |
15 kW |
25 hp |
MP75A4(R) |
67 A |
75 A |
112.5 A |
27 kW |
40 hp |
MP105A4(R) |
94 A |
105 A |
157.5 A |
37.5 kW |
60 hp |
MP155A4(R) |
139 A |
155 A |
232.5 A |
56 kW |
75 hp |
MP210A4(R) |
188 A |
210 A |
315 A |
75 kW |
125 hp |
MP350A4(R) |
295 A |
350 A |
525 A |
125 kW |
200 hp |
MP420A4(R) |
350 A |
420 A |
630 A |
150 kW |
250 hp |
MP550A4(R) |
450 A |
550 A |
825 A |
200 kW |
300 hp |
MP700A4(R) |
585 A |
700 A |
1050 A |
250 kW |
400 hp |
MP825A4(R) |
665 A |
825 A |
1237.5 A |
300 kW |
500 hp |
MP900A4(R) |
725 A |
900 A |
1350 A |
340 kW |
550 hp |
MP1200A4(R) |
1050 A |
1200 A |
1800 A |
450 kW |
750 hp |
MP1850A4(R) |
1570 A |
1850 A |
2775 A |
700 kW |
1150 hp |